Parameter and variable descriptions 6-45 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 101

Advertising
background image

PARAMETER AND VARIABLE DESCRIPTIONS

6-45

1557-UM050F-EN-P – June 2013



Idc Feedback [Idc feedback]
Linear number:

322

Minimum value:

0.000 pu

Maximum value:

2.000 pu

Analog Output Scaling: 5.0 V = 1.0 pu
This variable is the measured dc link current feedback.

Idc Error [Idc error]
Linear number:

323

Minimum value:

-2.000 pu

Maximum value:

2.000 pu

Analog Output Scaling: 5.0 V = 1.0 pu
This variable is the dc current error obtained by subtracting the dc current feedback from the dc current
reference.

V Line [V line]
Linear number:

324

Minimum value:

0.000 pu

Maximum value:

1.500 pu

Analog Output Scaling: 5.0 V = 1.0 pu
This variable is the measured line voltage. A value of 1.000 pu corresponds to rated motor voltage.

Vdc Reference [Vdc reference]
Linear number:

326

Minimum value:

-1.000

Maximum value:

1.000

Analog Output Scaling: 10.0 V = 1.0
This variable is the dc voltage reference, which is the output of the current regulator after the advance limit and
retard limit have been applied. A value of 1.000 corresponds to maximum positive voltage (motoring) and a
value of

–1.000 corresponds to maximum negative voltage (regenerating) regardless of the direction of motor

rotation.

Alpha Line [Alpha line]
Linear number:

327

Minimum value:

0.0 deg

Maximum value:

180.0 deg

Analog Output Scaling: 10.0 V = 360 degrees
This variable is the line converter firing angle, which is equal to the inverse cosine of the dc voltage reference.
It is in the range 0 to 90 degrees for motoring and 90 to 180 degrees for generating.

Alpha Machine [Alpha machine]
Linear number:

328

Minimum value:

0.0 deg

Maximum value:

359.9 deg

Analog Output Scaling: 10.0 V = 360 degrees
This variable is the machine converter firing angle. It is in the range 0 to 90 degrees for leading generating, 90
to 180 degrees for leading motoring, 180 to 270 degrees for lagging motoring, and 270 to 360 degrees for
lagging generating.