46 troubleshooting, Troubleshooting guide – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 288

Advertising
background image

10-46

TROUBLESHOOTING

1557-UM050F-EN-P – June 2013

Troubleshooting Guide

#

FAULT / ALARM

PROBABLE CAUSE

RECOMMENDED ACTION

1

LINE CONTACTOR WILL
NOT CLOSE IN TEST
MODE #3

1. MAINTAINED E. STOP

DEPRESSED


2. EXTERNAL EMERGENCY STOP

PB OR CUSTOMER‟S
PERMISSIVE CONTACTS NOT
CLOSED (IF PROVIDED)


3. RELAYS CR1 & CR2 NOT

ENERGIZED












4. THE AUXILIARY CONTACTS OF

CR2 DO NOT MAKE






5. CR & CR2 ENERGIZED BUT MAIN

CONTACTOR DOES NOT CLOSE

1A. RESET DRIVE E. STOP


2A. CHECK THE E-STOP CONTACT FROM

CUSTOMERS T-B TO DRIVE T-B




3A. CHECK FOR THE AVAILABILITY OF

CONTROL POWER

B. CHECK WHETHER START PB IS O.K.
C. CHECK FOR DRIVE PERMISSIVE FROM

CUSTOMERS PLC (IF ANY)

D. CHECK THE POSITION OF

NORMAL/OFF-TEST SELECTOR
SWITCH

E. CHECK THE INTEGRITY OF THE LINE

SIDE CONVERTER IN THE L.V. PANEL

F. CHECK THE COILS OF CR. & CR2

CONTACTORS


4A. CHECK THE AUXILIARY CONTACT

(DELAYED OPENING NC CONTACT) OF
MAIN CONTACTOR IN CR2 CONTROL
CIRCUIT

B. CHECK THE CONTACTS & REPLACE

THE CONTACTOR


5A.

CHECK THE “HC” & “CC” OF THE MAIN
CONTACTOR

2

INPUT CONTACTOR
WILL NOT HOLD IN

1. HOLDING COIL IS NOT

ENERGIZED

1A. CHECK THAT THE CONTROL WIRE

PLUG IS INSERTED PROPERLY

B. CHECK THE INTEGRITY OF THE

HOLDING COIL

C. CHECK FOR THE PRESENCE OF

METAL PARTICLES ON THE
ARMATURE

D.

CHECK THE GAP ON THE “M” MAIN
CONTACTOR AUXILIARY ASSEMBLY

3

DRIVE DOES NOT
RESPOND TO START
COMMAND


















1. NO CONTROL POWER











2. MEDIUM VOLTAGE NOT

PRESENT






3. FAULT ON DRIVE


1A. CHECK FOR THE AVAILABILITY OF

CONTROL POWER FROM CUSTOMER
(IF APPLICABLE)

B. CHECK THE MAIN ISOLATOR (IF

POWER IS FROM CPT) AND CLOSE IF
NECESSARY

C. CHECK THE CONTROL FUSES
D. CHECK THE INTEGRITY OF AUXILIARY

CONTACTS OF ISOLATOR

E. CHECK THE POSITION OF TEST/ OFF/

NORMAL SELECTOR SWITCH & TURN
THE POSITION TO NORMAL

2A. CHECK WHETHER MV IS AVAILABLE

FROM CUSTOMER‟S SIDE

B. CHECK THAT INPUT ISOLATOR IS

CLOSED

C. CHECK THE TRANSIENT

SUPPRESSION NETWORK FUSES.

D. CHECK THE MAIN FUSES
3A. CHECK THE PANELVIEW OR HIM

MODULE FOR ALARMS. DETERMINE
THE REASONS AND RESET

Continue…