Parameter and variable descriptions – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 112

Advertising
background image

6-56

PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013



SCANport Output [SCANport output]
Linear number:

399

Minimum value:

-4500 rpm

Maximum value:

4500 rpm

Analog Output Scaling: 10 V = 4096 rpm
This variable is the SCANport output, and indicates the motor speed in rpm.

Prior to Rev 4.60/5.00 this variable was located in the Analog I/O group with a linear number of 366.


Not Used [Not used]
Linear number:

400

Minimum value:

0

Maximum value:

65535

Analog Output Scaling: N/A
This is a dummy variable used to represent all non-existent variables in order to satisfy SCANport
requirements.