Parameter and variable descriptions 6-39 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 95

Advertising
background image

PARAMETER AND VARIABLE DESCRIPTIONS

6-39

1557-UM050F-EN-P – June 2013



Logic Status 1 [Logic status 1]
Linear number:

258

Minimum value:

0000 Hex

Maximum Value:

FFFF Hex

Analog Output Scaling: NA
This variable is the value of logic status 1, the status word that has the same definition for all drives. It is bit
encoded as shown below:

xxx1H - enabled
xxx2H - running
xxx4H - forward command
xxx8H - forward rotation

xx1xH - accelerating
xx2xH - decelerating
xx4xH - warning
xx8xH - fault

x1xxH - at speed command
x0xxH - port 0 local
x2xxH - port 1 local
x4xxH - port 2 local
x6xxH - port 3 local
x8xxH - port 4 local
xAxxH - port 5 local
xCxxH - port 6 local
xExxH - no local

0xxxH - external speed command 0 selected (analog input 1L)
1xxxH - preset speed command 1 selected
2xxxH - preset speed command 2 selected
3xxxH - preset speed command 3 selected
4xxxH - preset speed command 3 selected
5xxxH - preset speed command 3 selected
6xxxH - preset speed command 3 selected
7xxxH - preset speed command 3 selected
8xxxH - external speed command 8 selected (analog input 1M)
9xxxH - port 1 speed command selected
AxxxH - port 2 speed command selected
BxxxH - port 3 speed command selected
CxxxH - port 4 speed command selected
DxxxH - port 5 speed command selected
ExxxH - port 6 speed command selected
FxxxH - preset jog speed command selected

Advertising