Parameter and variable descriptions 6-47 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 103

Advertising
background image

PARAMETER AND VARIABLE DESCRIPTIONS

6-47

1557-UM050F-EN-P – June 2013



V Stator [V stator]
Linear number:

344

Minimum value:

0.000 pu

Maximum value:

1.500 pu

Analog Output Scaling: 5.0 V = 1.0 pu
This variable is the calculated stator voltage magnitude. It varies with both speed and torque and if the flux
command is set correctly should be about 1.0 pu at rated speed and rated load. The stator voltage may be
less than 1.0 pu at rated speed if the load torque is less than rated or the line voltage is low.

Torque [Torque]
Linear number:

345

Minimum value:

-1.500

Maximum value:

1.500

Analog Output Scaling: 5.0 V = 1.0
This variable is the calculated motor torque. A value of 1.000 corresponds to rated torque. It is positive for
forward torque and negative for reverse torque.

Prior to Rev 4.60/5.00, this variable was scaled in per unit based on the motor rated kVA and was about 10%
lower.


Motor Power [Motor power]
Linear number:

346

Minimum value:

-1.500

Maximum value:

1.500

Analog Output Scaling: 5.0 V = 1.0
This variable is the calculated motor power. A value of 1.000 corresponds to rated power. It is positive for
motoring and negative for generating regardless of the direction of rotation.

Prior to Rev 4.60/5.00, this variable was scaled in per unit based on the motor rated kVA and was about 10%
lower.


V Neutral Motor [V neutral motor]
Linear number:

347

Minimum value:

0.000 pu

Maximum value:

1.500 pu

Analog Output Scaling: 5.0 V = 1.0 pu
This variable is the measured motor neutral to ground voltage.

Tachometer Feedback [Tach feedback]
Linear number:

348

Minimum value:

-100.0 Hz

Maximum value:

100.0 Hz

Analog Output Scaling: 1.0 V = 12.8 Hz
This variable is the motor speed measured using the optional tachometer or encoder. It is positive for forward
rotation and negative for reverse rotation.