Commissioning 9-17 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 217

Advertising
background image

COMMISSIONING

9-17

1557-UM050F-EN-P – June 2013

Rectifier Power Supply Readings 18-pulse Bridge

BOARD COMBINATION

POSITIVE RAIL

TP4 to TP15

NEGATIVE RAIL

TP3 to TP15

80165-178-52 with 80165-158-51/53/54

+22.50V to +23.00V

-5.0V to -6.0V

80165-698-52 with 80165-158-51/53/54

+22.50V to +23.00V

-5.0V to -6.5V

NOTE: Adjust the voltage at TP4 first and then verify that the voltage at TP3 is within the range

described.

Voltage Drift Limits
The maximum allowable drift range for the positive rail is between +27.25 V and +18.25 V
The maximum allowable drift range for the negative rail is between -7.0V and -4.3V




SLAVE 2 Bridge (Plus 20 Degree Winding)

1C

3C

5C

4C

6C

2C




SLAVE 1 Bridge (Minus 20 Degree Winding)

1B

3B

5B

4B

6B

2B




MASTER Bridge

1A

3A

5A

4A

6A

2A

Advertising