PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013



Current Feedback Rated Line [I fbk rated line]
Linear number:

159

Minimum value:

0.500 V

Maximum value:

2.500 V

Default value:

N/A

This parameter specifies the rated line current feedback in volts rms calculated from the line CT ratio and
burden and the rated motor current. It is not saved and is recalculated when any of the parameters affecting its
value are changed. The nominal value is 1.768 V. A warning will be displayed if this parameter is out of range.

Current Feedback Rated Motor [I fbk rated motor]
Linear number:

160

Minimum value:

0.500 V

Maximum value:

2.500 V

Default value:

N/A

This parameter specifies the rated motor current feedback in volts rms calculated from the motor CT ratio and
burden and the rated motor current. It is not saved and is recalculated when any of the parameters affecting its
value are changed. The nominal value is 1.768 V. A warning will be displayed if this parameter is out of range.


11 Line Converter Protection Parameters

Line Overcurrent Trip [Line O/C trip]
Linear number:

161

Minimum value:

0.00 pu

Maximum value:

2.00 pu

Default value:

1.50 pu

This parameter specifies the level the line current must exceed before a line overcurrent fault is indicated.

NOTE: For current ratings near the maximum for the drive frame size, this parameter will be automatically
limited to a maximum value less than 2.00. This feature was added in Rev 4.62/5.11.


Line Overcurrent Delay [Line O/C delay]
Linear number:

162

Minimum value:

0.000 sec

Maximum value:

0.040 sec

Default value:

0.004 sec

This parameter specifies the time the line current must remain above the trip level before a line overcurrent
fault is indicated.

Line Overload Trip [Line O/L trip]
Linear number:

163

Minimum value:

0.20 pu

Maximum value:

1.15 pu

Default value:

1.00 pu

This parameter specifies the maximum continuous operating current of the drive.

Line Overload Delay [Line O/L delay]
Linear number:

164

Minimum value:

0 sec

Maximum value:

61 sec

Default value:

60 sec

This parameter specifies the time the drive may operate at 1.5 times the overload trip level before a line
converter overload fault is indicated.