48 troubleshooting – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 290

Advertising
background image

10-48

TROUBLESHOOTING

1557-UM050F-EN-P – June 2013

#

FAULT / ALARM

PROBABLE CAUSE

RECOMMENDED ACTION

4

LINE SIDE CONVERTER
DEVICE SHORTED

1. DEVICE SHORTED BY

EXTERNAL MEANS



2. GATE DRIVER DIAGNOSTIC

CIRCUIT FAILURE



3. DEVICE FAILURE HAS

OCCURRED



4. IMPROPER VOLTAGE

FEEDBACK

1A. CHECK SNUBBER CIRCUIT
B. CHECK THE WIRING
C. CHECK THE FIBER OPTIC CABLE

2A. CHECK FOR GATE SIGNALS IN TEST

MODE 1; IF NO SIGNAL, REPLACE THE
BOARDS


3A. CHECK THE RESISTANCE OF DEVICE.

REPLACE THE MATCHED SET OF
DEVICES IF THE DEVICE READS ZERO
OHMS

4A. CHECK THE VOLTAGE FEED BACK

CIRCUITS AND RESISTORS

5

MACHINE SIDE
CONVERTER DEVICE
SHORTED

1. DEVICE SHORTED BY

EXTERNAL MEANS



2. GATE DRIVER BOARD FAILURE










3. DRIVE NOT STABLE

1A. CHECK THE SNUBBER NETWORK
B. CHECK THE WIRING
C. CHECK THE FIBER OPTIC CABLE

2A. CHECK THE FUSES ON THE IGDPS.

REPLACE FUSE, IF BLOWN

B. CHECK FOR THE GATING PULSES.

IF NO PULSES, REPLACE THE GATE
DRIVER BOARD

C. CHECK THE POWER SUPPLY BOARD.

IF THE POWER SUPPLY READINGS DO
NOT ADJUST, REPLACE THE BOARD

D. CHECK THE VOLTAGE SHARING

RESISTORS


3A. MONITOR MACHINE FLUX SIGNAL AND

CHECK FOR OSCILLATIONS IN DRIVE
SPEED OR CURRENT AND RE-TUNE IF
NECESSARY.

6

NO DISPLAY ON PANEL
VIEW

1. PANEL VIEW DEFECTIVE




2. NO POWER SUPPLY

3. NO COMMUNICATION







4. LIGHT BULB IS BURNT OUT.

1A. CHECK POWER SUPPLY
B. CHECK THE CPB HEALTHY LED IS ON
C. CHECK THE RIBBON CABLES
D. REPLACE PANEL VIEW

2A. CHECK CONTROL POWER SUPPLY

3A. CHECK FOR THE HEALTHY GREEN

LED ON COMMUNICATION
PROCESSOR BOARD

B. CHECK THE CABLE BETWEEN

COMMUNICATION PROCESSOR
BOARD AND PANEL VIEW

C. REBOOT THE PANEL VIEW

4.

REPLACE THE BULB.

7

INPUT POWER STAYS
ON WHEN ISOLATOR
SWITCH IS IN OFF
POSITION

1. ISOLATION SWITCH DEFECTIVE

1A. THE ISOLATION SWITCH BLADES

REMAIN ENGAGED WHEN THE
SWITCH IS IN OFF POSITION ISOLATE
THE POWER FROM INCOMING
BREAKER, CHECK THE ISOLATION
SWITCH MECHANISM

8

AC CONTROL POWER
FAULT

1. LOSS OF AC POWER

1A. CHECK FOR THE PRESENCE OF

CONTROL POWER

B. CHECK THE LEVEL OF INCOMING

CONTROL POWER SUPPLY >85%

C. CHECK THE ANNUNCIATION MODULE
D. REPLACE THE ANNUNCIATION