PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013



Speed Command 9 Minimum [Speed cmd 9 min]
Linear number:

45

Minimum value:

127.0 Hz

Default value:

6.0 Hz

This parameter specifies the value of speed command corresponding to a digital speed command input of 0.
The required value can be calculated using the following formula:

Speed cmd 9 min = fmin + [vmin x (fmax-fmin) / (vmax-vmin)]

fmin is the minimum operating speed

fmax is the maximum operating speed

vmin is the value corresponding to minimum operating speed

vmax is the value corresponding to maximum operating speed


Speed Command 9 Maximum [Speed cmd 9 max]
Linear number:

46

Minimum value:

0.0 Hz

Maximum value:

127.0 Hz

Default value:

60.0 Hz

This parameter specifies the value of speed command corresponding to a digital speed command input of
32767. It may be less than Speed Command 9 Minimum. The required value can be calculated using the
following formula:

Speed cmd 9 max = fmin + [(32767-vmin) x (fmax-fmin) / (vmax-vmin)]


The terms are as defined in the description of parameter Speed Command 9 Minimum.

Speed Command Minimum [Speed cmd min]
Linear number:

47

Minimum value:

1.0 Hz

Maximum value:

75.0 Hz

Default value:

6.0 Hz

This parameter specifies the minimum value of the speed command. When the drive is running, the absolute
value of the speed command will not be less than this value regardless of the other parameter settings (except
for Speed Command Maximum).

Speed Command Maximum [Speed cmd max]
Linear number:

48

Minimum value:

1.0 Hz

Maximum value:

75.0 Hz

Default value:

60.0 Hz

This parameter specifies the maximum value of the speed command. The absolute value of the speed
command will not be greater than this value regardless of the other parameter settings (including Speed
Command Minimum).


4 Skip Speed Parameters

Skip Speed 1-4 [Skip speed 1-4]
Linear numbers:

49-52

Minimum value:

6.0 Hz

Maximum value:

90.0 Hz

Default value:

90.0 Hz

These four parameters specify the center of the skip speed zones.