28 commissioning – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 228

Advertising
background image

9-28

COMMISSIONING

1557-UM050F-EN-P – June 2013

COMMUTATION INDUCTANCE TUNED CORRECTLY

COMMUTATION INDUCTANCE INCORRECTLY TUNED



10.

Set parameter "Idc command test" to 0.800 pu. The dc current will increase and the commutation
notches will become much larger.


11.

Repeat steps 6 to 9. The higher current will produce a more accurate measurement of the commutation
inductance.


12.

Confirm that the commutation inductance is set to the correct value by increasing the horizontal and
vertical magnification and observing the zero crossing of reconstructed voltage F12. Because the line
converter firing angle is about 90 degrees, the commutation notch occurs near the zero crossing of the
reconstructed voltage. The signal should be a straight line through the zero crossing with almost no
visible distortion. Either increasing or decreasing parameter “ L Commutation“ should cause the distortion
to increase.


13.

Stop the drive. Set parameters “Test mode” and "Idc command test" to zero.



2. Current Regulator

The tuning of the current regulator is controlled by three parameters in the “P Current Control" group:

1. “Curreg bandwidth”

2. "L dc link”

3. "T dc link"


Of these three parameters, inductance “L dc link“ is calculated from its nameplate rating, the current regulator
bandwidth should be set to its default value of 200 rad/sec, and only “T dc link” is unknown and must be
measured. Although the current regulator was tuned during factory test, it should be retuned during
commissioning because the dc link time constant is affected by the impedance of the drive input transformer.

Current Regulator Autotuning

The current regulator can be tuned automatically using the following procedure:

1.

Ensure that the parameters in the "P Nameplate" group have been set to the correct values, otherwise the
calculated value of parameter "L dc link" in "P Current Control" will not be correct.


2.

Set parameter "Autotune select" in "P Autotune" to 2. The drive will go into dc current test mode. The
current re

gulator bandwidth is temporarily set to the value specified by parameter "Autotune Idc BW”. The

dc current command is set to the value specified by parameter "Autotune Idc cmd". The dc current step is
set to the value specified by parameter "Autotune Idc stp".