Parameter and variable descriptions – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 82

Advertising
background image

6-26

PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013



Motor Unbalance Delay [Motor U/B delay]
Linear number:

184

Minimum value:

0.00 sec

Maximum value:

10.00 sec

Default value:

2.00 sec

This parameter specifies the time the motor current unbalance must remain above the trip level before a motor
unbalance fault is indicated.


This parameter was added in Rev 5.30 and is not present in 4.xx.


Motor Over Speed Trip [Over speed trip]
Linear number:

185

Minimum value:

10 Hz

Maximum value:

100 Hz

Default value:

66 Hz

This parameter specifies the level the motor speed must exceed before a motor overspeed fault is indicated.

Motor Overspeed Delay [Overspeed delay]
Linear number:

186

Minimum value:

0.00 sec

Maximum value:

10.00 sec

Default value:

0.50 sec

This parameter specifies the time the motor speed must exceed the trip level before a motor overspeed fault is
indicated.

Motor DC Link Over Voltage Trip [Mtr DC O/V trip]
Linear number:

187

Minimum value:

0.10 pu

Maximum value:

1.47 pu

Default value:

1.47 pu

This parameter specifies the level the machine side dc link voltage must exceed before a dc link over voltage
fault is indicated.

DC Link Overvoltage Delay [DC O/V delay]
Linear number:

188

Minimum value:

0.000 sec

Maximum value:

0.040 sec

Default value:

0.004 sec

This parameter specifies the time the machine side dc link voltage must remain above the trip level before a dc
link overvoltage fault is indicated.

Note: For Bulletin 1557M drives this parameter is internally limited to 0.004 sec maximum.

Ground Fault Overvoltage Trip [Gnd flt O/V trip]
Linear number:

189

Minimum value:

0.00 pu

Maximum value:

1.50 pu

Default value:

0.20 pu

This parameter specifies the level the motor neutral to ground voltage must exceed before a ground fault
overvoltage is indicated.

Note: The value of this parameter must be increased for drives without isolation transformers because the
neutral to ground voltage will be quite high in normal operation.