Troubleshooting 10-47 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 289

Advertising
background image

TROUBLESHOOTING

10-47

1557-UM050F-EN-P – June 2013

#

FAULT / ALARM

PROBABLE CAUSE

RECOMMENDED ACTION

3


DRIVE DOES NOT
RESPOND TO START
COMMAND (CONT‟D)


4. LOCAL/REMOTE SWITCH IN

WRONG POSITION




5. NORMAL/OFF/TEST SELECTOR

IN OFF POSITION

6. NO DC POWER


7. GREEN LED OFF ON DRIVE

CONTROL BOARD




8. LEDs ON DRIVE I/O BOARD ARE

OFF


9. NO COMMAND FROM

CUSTOMER‟S PLC





10. REMOTE I/O COMMUNICATION

MODULE INDICATING ERROR





11. NO POWER SUPPLY TO

TACHOMETER
(IF EQUIPPED)



12. DEFECTIVE MOTOR OUTPUT

CAPACITORS


4A. POSITION OF THE SWITCH TO

PROPER POSITION

B.

CHECK THE INTEGRITY OF
CONTACTS

C. CHECK THE REMOTE I/O BOARD FOR

PROPER LED TO BE ON

5A SWITCH TO NORMAL POSITION

6A. CHECK FOR THE PRESENCE OF AC

CONTROL VOLTAGE

B. CHECK FOR DC VOLTAGE FROM

DC/DC CONVERTER

7A. CHECK FOR THE +5V, +15v, -15V AT

DOB‟s

B. REPLACE THE FIRMWARE CHIPS
C. CHECK THAT THE RIBBON CABLES

ARE IN POSITION

D. REPLACE THE DCBs

8A. CHECK THE RIBBON CABLE FROM

LINE DCB TO I/O BOARD

B. CHECK FOR CONTROL POWER AT I/O

BOARD

9A. CHECK WHY CUSTOMER SIDE PLC

RUN COMMAND IS NOT PRESENT

B. IF A REMOTE I/O COMMUNICATION

MODULE (1203) IS USED, CHECK THE
DIP SWITCHES FOR PROPER
CONFIGURATION

10A. CHECK THAT THE C.P.B. IS

FUNCTIONAL (GREEN LED ON)

B. CHECK THE RIBBON CABLES FROM

C.P.B. TO BUL 1203 GD1

C. CHECK THE POWER SUPPLY AT 1203 GDI
D. CHECK WHETH

ER CUSTOMER‟S

CABLES ARE TERMINATED AT 1203 GD1

11A. CHECK THE POWER SUPPLY TO

TACHOMETER

B. CHECK THE CABLING TO

TACHOMETER

C. CHECK THE FUNCTIONALITY OF THE

TACHOMETER

12A. CHECK THE INTEGRITY OF THE

MOTOR OUTPUT CAPACITORS BY
MEGGERING/CHARGE- DISCHARGE
METHOD