TROUBLESHOOTING

10-35

1557-UM050F-EN-P – June 2013

Drive Faults

Fault

Code #

FAULT

MESSAGE

F

Description

F24

Mtr stall

F

The drive has detected a motor stall condition.

F25

dc\dc fail

F

The dc\dc converter has reported a failure in one or more of the non-
redundant outputs or both outputs of the redundant supplies have
failed. The threshold for fail condition is 95% of rated output voltage.

F26

Mtr thy open

F

An open GTO has been detected in the machine converter. A GTO
failure is detected before starting or when the motor voltage exceeds
0.25 pu, after starting.

F27

Mtr thy short

F

A shorted GTO has been detected in the machine converter. A GTO
failure is detected before starting or when the motor voltage exceeds
0.25pu, after starting.

F28

DC cntrl pwr

F

The 48Vdc-power supply has reported a DC voltage fault. Check
control power supply.

F29

Mtr unbalance

F

The unbalance in the motor current feedback has exceeded the level
in P183 for the duration in P184, or the unbalance in the motor flux
feedback has exceeded 0.1 pu for 100 cycles.

F30

Output open

F

The output contactor has opened when the drive was running.

F31

No Vdc fdbk

F

No machine side dc link voltage feedback detected during the GTO
gating test when the drive is started. Usually indicates that the dc
voltage feedback is not connected

F32

Drv overload

F

The drive overload rating in P163 has been exceeded for the
duration in P164.

F33

Mtr overload

F

The motor overload rating in P179 has been exceeded for the
duration in P180.

F34

Mtr over spd

F

The motor speed feedback has exceeded P185 for the duration in
P186

F35

Control temp

F

Temperature on the drive control board is above 70 degrees
centigrade. Firmware revision numbers less than 5.00 this warning
not implemented

F36

Syncxfer fail

F

A synchronous transfer was not completed within the time specified
by P230. The drive will stop.

F37

Neutral o/v

F

The motor Neutral to Ground voltage has exceeded the level in P189
for the duration in P190.

F38

SCANport flt

F

This fault indicates that one of the four non-maskable Scan ports
warning have occurred.
1. Communication Processor board failure (comm proc brd)
2. Loss of adapter (Adapter loss)
3. Speed command loss (spdcmd loss)
4. Loss of local control (Local loss)

F39

Fan Loss

F

The output of the static pressure sensor fell below 80% of the level in
P175 for the duration in P176.

F40

Over temp 1

F

Heatsink over temperature is present, 85 degrees centigrade exceeded.

F41

Over temp 2

F

Heatsink over temperature is present, 85 degrees centigrade exceeded.

F42

Over temp 3

F

Heatsink over temperature is present, 85 degrees centigrade exceeded.

F43

Under temp

F Heatsink temperature is below

40 degrees centigrade.