6-52

PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013



Fault Flags External [Fault flags ext]
Linear number:

372

Minimum value:

0000 Hex

Maximum value:

FFFF Hex

Analog Output Scaling: N/A
This variable is the external fault flags. Unlike the other faults, the fault message and the class of each of these
faults is user definable. It is bit encoded as shown below:

xxx1H - external 1 [512]
xxx2H - external 2 [513]
xxx4H - external 3 [514]
xxx8H - external 4 [515]
xx1xH - external 5 [516]
xx2xH - external 6 [517]
xx4xH - external 7 [518]
xx8xH - external 8 [519]
x1xxH - external 9 [520]
x2xxH - external 10 [521]
x4xxH - external 11 [522]
x8xxH - external 12 [523]
1xxxH - external 13 [524]
2xxxH - external 14 [525]
4xxxH - external 15 [526]
8xxxH - external 16 [527]

Warning Flags A [Warning flags A]
Linear number:

373

Minimum value:

0000 Hex

Maximum value:

FFFF Hex

Analog Output Scaling: N/A
This variable is the maskable drive warning flags. It is bit encoded as shown below.

xxx1H - drive overload warning
xxx2H - motor overload warning
xxx4H - line under voltage
xxx8H - line reverse sequence
xx1xH - input contactor open
xx2xH - input contactor closed
xx4xH - output contactor open
xx8xH - output contactor closed
x1xxH - bypass contactor open
x2xxH - bypass contactor closed
x4xxH - tach loss
x8xxH - h/w overcurrent warning
1xxxH - h/w overvoltage warning
2xxxH - tach rotation
4xxxH - line synchronization loss
8xxxH

– dc/dc converter failure (Rev 5.32 only)