18 commissioning – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 218

Advertising
background image

9-18

COMMISSIONING

1557-UM050F-EN-P – June 2013

Inverter Power Supply Readings

800 / 1500 AMP G.T.O.

BOARD COMBINATIONS

POSITIVE RAIL

TP5 to TP15

NEGATIVE RAIL

TP3 to TP15

80165-178-51 with 80165-138-53/54

+7.5V to +8.8V

-12.45V to -12.55V

80165-698-51 with 80165-138-53

+7.5V to +9.0V

-12.45V to -12.55V

80165-698-51 with 80165-138-54

+7.5V to +10.0V

-12.45V to -12.55V

NOTE: Adjust the voltage at TP3 first and then verify that the voltage at TP5 is within the range
described.

Voltage Drift Limits
The maximum allowable drift range for the positive rail is between+10.0V and +7.0V
The maximum allowable drift range for the negative rail is between -15.0V and -11.5V

BOARD COMBINATIONS
80165-958-51 with 80190-058-51/52

NOTE: Self-calibrating no adjustment
required. Verify voltage values only.

POSITIVE RAIL

TP20 to TP32

+8.60 to +9.40

NEGATIVE RAIL

TP16 to TP32

-12.10 to -12.90

3000 AMP G.T.O.

BOARD COMBINATION
80165-958-53 with 80165-978-53

NOTE: Self-calibrating no adjustment
required. Verify voltage values only.

POSITIVE RAIL

TP17 to TP18

+12.50V to +13.50V

TP10 to TP5

+7.80V to +8.20V

NEGATIVE RAIL

TP13 to TP5

-19.70V to -20.30V

BOARD COMBINATION
80165-958-53 with 80190-058-53

NOTE: Self-calibrating no adjustment
required. Verify voltage values only.

POSITIVE RAIL

TP20 to TP32

+12.60 to +13.40

NEGATIVE RAIL

TP16 to TP32

-19.60 to -20.40

BOARD COMBINATION
80165-178-51 with 80165-758-53

NOTE: Adjust the voltage at TP13 first and
then verify that the voltage at TP19 is
within the range described.

POSITIVE RAIL

TP19 to TP16

+11.40V to +12.60V

NEGATIVE RAIL

TP13 to TP16

-19.90V to -20.10V