TROUBLESHOOTING

10-37

1557-UM050F-EN-P – June 2013

Drive Faults

Fault

Code #

FAULT

MESSAGE

F

Description

F282

Syncxfer fail

W A synchronous transfer was not completed within the time specified

by parameter Sync xfer time (P230). The drive will continue to run.

F283

Not used

W

F284

Com proc brd

W

Indicates that the communication board is not communicating with
drive control board or the board has failed self-power test, which
requires recycling of the power.

F285

Adapter loss

W The drive has lost communication with a SCANport adapter.

F286

Spd cmd loss

W

The drive has lost communication with the SCANport adapter
providing the speed command.

F287

Local loss

W

F288

Tuning abort

W Autotuning was unable to complete the measurement of the tuning

parameter with in allowed time.

F289

In test mode

W Indicated that the drive is set in a test mode

F290

Reg in limit

W Speed regulator or flux regulator hit the limit during auto tuning and

the auto tune results are not valid.

F291

R stator hi

W Indicated the motor cables are extremely long.

F292

Time limit

W Indicates the autotuning could not measure the parameter with in

allowed time limit.

F293

Inertia high

W Indicates that the measure inertia is greater than 5.0 sec.

F294

L comm low

W Indicates the measured commutation inductance is less than 0.02

pu. Require manual tuning of commutation inductance.

F295

L comm high

W Indicates the measured commutation inductance is greater than

0.15pu. Require manual tuning of the commutation inductance.

F296

T dc low

W Indicates the measured DC link time constant is less than 0.020 sec.

Require manual tuning of DC link time constant.

F297

T dc high

W Indicates the measured DC link time constant is greater than

0.100sec. Require manual tuning of DC link time constant.

F298

L leakage lo

W Indicates the measured leakage inductance is less than 0.15pu.

F299

L leakage hi

W Indicates the measured leakage inductance is greater than 0.30pu.

F300

L magn low

W Indicates the measured magnetising inductance is less than 2.0pu.

Require manual tuning for flux regulator.

F301

L magn hi

W Indicates the measured magnetising inductance is greater than

10.0pu. Require manual tuning for flux regulator.

F302

T rotor low

W Indicates the measure rotor time constant is less than 0.2sec.

It requires manual tuning of rotor time constant.

F303

T rotor high

W Indicates the measure rotor time constant is greater than 5.0sec.

It requires manual tuning of rotor time constant.