COMMISSIONING

1557-UM050F-EN-P – June 2013


To assign external panel meters or analog ports, press the "SETUP"
(F8) softkey from the top level main menu.. From the SETUP menu in
the figure press the "ANALOG" (F2) softkey. There are two pages of
assignments shown below in the figures. Use the arrow keys to select
a port and from the menu's displayed after, select a variable to assign
to it.



From the main screen, press the "SETUP" (F8) softkey. Then press
the "PARAMS" (F7) softkey. From the parameter select group
screen, use the "NEXT PAGE" (F8) softkey to arrive at page 2. Use
the arrow keys to cursor down to "P Analog Output", and press enter.





It will be necessary to set up the analog scale outputs. After
determining to which outputs the metering is connected, calculate the
scale, from the equations below. Once this is obtained, cursor to the
correct analog scale output and press enter.




Enter the calculated value and press return, then press the F10
softkey to exit.