PARAMETER AND VARIABLE DESCRIPTIONS

6-19

1557-UM050F-EN-P – June 2013



10 Converter Parameters

Series Thyristor Line [Series thy line]
Linear number:

145

Minimum value:

1

Maximum value:

6

Default value:

1

This parameter specifies the number of series thyristors in each of the 6 legs of the line converter.

Series Thyristor Motor [Series thy motor]
Linear number:

146

Minimum value:

1

Maximum value:

6

Default value:

1

This parameter specifies the number of series GTO thyristors in each of the 6 legs of the machine converter.

Redundant Thyristor Line [Redundt thy line]
Linear number:

147

Minimum value:

0

Maximum value:

1

Default value:

0

This parameter specifies the number of redundant thyristors in each of the 6 legs of the line converter.

Redundant Thyristor Motor [Redundt thy mtr]
Linear number:

148

Minimum value:

0

Maximum value:

1

Default value:

0

This parameter specifies the number of redundant GTO thyristors in each of the 6 legs of the machine
converter.

CT Ratio Line [CT ratio line]
Linear number:

149

Minimum value:

10

Maximum value:

10000

Default value:

200

This parameter specifies the ratio of the current transformers used for line current feedback.

CT Ratio Motor [CT ratio motor]
Linear number:

150

Minimum value:

10

Maximum value:

10000

Default value:

2500

This parameter specifies the ratio of the current transducers (LEMs) used for motor current feedback.