Parameter and variable descriptions – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 120

Advertising
background image

6-64

PARAMETER AND VARIABLE DESCRIPTIONS

1557-UM050F-EN-P – June 2013


24

Analog I/O Variables

Name

Minimum

Maximum

1.0V =

Units

353

Analog Input 1L

-10.00

9.99

1.0

V

355

Analog Input 1M

-10.00

9.99

1.0

V

356

Analog Input 2M

-10.00

9.99

1.0

V

357

Analog Output 5L

-10.00

9.92

1.0

V

358

Analog Output 6L

-10.00

9.92

1.0

V

359

Analog Output 5M

-10.00

9.92

1.0

V

360

Analog Output 6M

-10.00

9.92

1.0

V

361

Current Meter

0

1000

12.8

A

362

Voltage Meter

0

8000

409.6

V

363

Speed Meter

-4500

4500

409.6

rpm

364

Power Meter

-7500

7500

102.4

kw

365

Analog Output 4L

-10.00

9.92

1.0

V

366

Analog Output 4M

-10.00

9.92

1.0

V

367

Gnd Flt Current

0.0

10.0

1.28

A

368

Control Board Temperature

-40

100

6.25

C


25

Fault and Warning Variables

Name

Minimum

Maximum

1.0V =

Units

369

Fault Flags 1L

0000H

FFFFH

NA

370

Fault Flags 1M

0000H

FFFFH

NA

371

Fault Flags 2

0000H

FFFFH

NA

372

Fault Flags External

0000H

FFFFH

NA

373

Warning Flags A

0000H

FFFFH

NA

374

Warning Flags B

0000H

FFFFH

NA

376

PLC Error Flags

0000H

FFFFH

NA

377

Autotune Warning Flags

0000H

FFFFH

NA

382

Fault Output

0.00

9.92

1.0V

V


26

Control Owner Variables

Name

Minimum

Maximum

1.0V =

Units

385

Stop Owner

00H

FFH

NA

386

Local Owner

00H

FFH

NA

387

Start Owner

00H

FFH

NA

388

Direction Owner

00H

FFH

NA

389

Jog Owner

00H

FFH

NA

391

Fault Reset Owner

00H

FFH

NA

392

Speed Command Owner

00H

FFH

NA

393

Sync Transfer Owner

00H

FFH

NA

398

SCANport Input

0

32767

3276.7

399

SCANport Output

-4500

4500

409.6

rpm

400

Not Used

0

65535

NA