GTO Gate Driver Board Calibration and Gate Pulse Verification Procedure
(800 or 1500 Amp Devices)

The following procedure must be followed when the GTOGD and/or IGDPS boards are replaced. This
procedure must also be followed whenever MACHINE SIDE CONVERTER devices are replaced.

Tools Required:

Digital Multimeter

100 Meg Hz Oscilloscope

Minigrabber meter probes

Potentiometer Screwdriver


1. Close the circuit breaker in the drives control logic section to apply the 50 volts DC power to the

Isolated Gate Driver Power Supply Board (IGDPS). The green LED on the Gate Driver should
illuminate. If it does not illuminate, check the followings:

2A fuse on the GTOGD board

The connections from flyback transformer on IGDPS board to GTOGD board

50 V DC at IGDPS board

The multi-turn potentiometer P1 is set to minimum value, the potentiometer is located at the center

of IGDPS board.

If all above is correct, replace the IGDPS board.


2. Wait 10 minutes for the board to warm-up and stabilize.

3. Connect the negative lead of the Multimeter to test point TP15 located on the lower right corner of the

GTOGD board and connect the positive lead to test point TP3 located in the upper left corner of
GTOGD board.


4. Adjust the multi-turn potentiometer P1 located in the center of the IGDPS board for the voltage range

indicated in the table below.


5. Remove the positive meter lead from TP3 and connect it to adjacent test point TP5 on GTOGD board.

Verify that the voltages within the voltage range indicated in the table below.

BOARD COMBINATION

POSITIVE RAIL

@

TP5 to TP15

NEGATIVE RAIL

@

TP3 to TP15

80165-178-51 with 80165-138-51/52/53/54

+7.5V to +8.8V

-12.45V to -12.55V

80165-698-51 with 80165-138-53

+7.5V to +9.0V

-12.45V to -12.55V

80165-698-51 with 80165-138-54

+7.5V to +10.0V

-12.45V to -12.55V


6. The board calibration is now complete.

7. Put the drive in TEST MODE 1 and start the drive.

8. Connect the oscilloscope probes to the gate and cathode terminals on the SCRGD board and verify

the gate pulse waveform is as indicated in the example below.