Troubleshooting 10-29, Gto & scr replacement instruction sheet – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 271

Advertising
background image

TROUBLESHOOTING

10-29

1557-UM050F-EN-P – June 2013


NOTE: The following Figure shows the line side converter heatsink stack assembly. Some type of
machine side converter heatsink stack assembly does not have the bottom nuts on the fiberglass-
clamping rod and the device orientation is in downward direction. The procedure to loosen the
machine and line side heatsink stacks is the same.

ALLEN-BRADLEY

GTO & SCR REPLACEMENT INSTRUCTION SHEET

For assemblies with FIBERGLASS CLAMPING RODS

Dwg. 80098-925(2)

Figure 10.6