Parameter and variable descriptions 6-57 – Rockwell Automation 1557 MEDIUM VOLTAGE AC DRIVE User Manual

Page 113

Advertising
background image

PARAMETER AND VARIABLE DESCRIPTIONS

6-57

1557-UM050F-EN-P – June 2013

Parameters and Variables Listed by Group

Categories:

1 - rating or configuration parameter set at the factory
2 - application parameter set at the factory or at commissioning
3 - tuning parameter set at commissioning
S - synchronous drive parameter not used for induction motors

All other parameters are normally left at the default setting.

1

Feature Select

Name

Minimum

Maximum

Default

Units

Cat.

1

Contactor Configuration

0

7

0

2

3

Automatic Restart Delay

0.000

10.000

0.000

sec

2

4

Test Mode

0

4

0

6

Speed Command Select 0

1

15

1

2

7

Speed Command Select

0

15

NA

8

Reverse Enable

0

1

0

2

9

Speed Command Select 8

1

15

9

2

10

Contactor Open Delay

0.0

57.0

0.0

min

2

13

Parameter Level

0

3

2

15

Drive Control FRN

0.00

99.99

NA

16

Communications Proc FRN

0.00

99.99

NA


2

Nameplate Parameters

Name

Minimum

Maximum

Default

Units

Cat.

17

Rated Line Frequency

50

60

60

Hz

1

20

Capacitor kvar

1

7500

100

kvar

1

21

Capacitor Volts

1000

10000

2400

V

1

22

Rated Motor Volts

1000

7200

2300

V

1

23

Rated Motor Amps

10

1000 or 1400

60

A

1

24

Rated Motor kw

30

7500 or 10000 187

kw

1

25

Rated Motor hp

40

10000 / 13400 250

hp

1

26

Rated Motor rpm

150.0

3600.0

1185.0

rpm

1

27

Link Inductance

1.0

600.0

64.0

mh

1

28

Capacitor Frequency

50

60

60

Hz

1

29

Rated Motor Frequency

40

90

60

Hz

1

30

Motor Type

0

1

0

1

31

Service Factor

0.75

1.25

1.00

1

32

Drive Type

0

1

0

1


3

Speed Command Parameters

Name

Minimum

Maximum

Default

Units

Cat.

33

Preset Speed Command 1

0.5

90.0

30.0

Hz

34

Preset Speed Command 2

0.5

90.0

35.0

Hz

35

Preset Speed Command 3

0.5

90.0

40.0

Hz

40

Preset Jog Speed

1.0

60.0

6.0

Hz

41

Speed Command 0 Minimum

-127.0

127.0

6.0

Hz

2

42

Speed Command 0 Maximum

0.0

127.0

60.0

Hz

2

43

Speed Command 8 Minimum

-127.0

127.0

6.0

Hz

2

44

Speed Command 8 Maximum

0.0

127.0

60.0

Hz

2

45

Speed Command 9 Minimum

0.0

127.0

6.0

Hz

2

46

Speed Command 9 Maximum

0.0

127.0

60.0

Hz

2

47

Speed Command Minimum

1.0

75.0

6.0

Hz

2

48

Speed Command Maximum

1.0

75.0

60.0

Hz

2

Advertising