Priority: Here you can adjust the priority of the event. 20 is the lowest, 0 is the highest.

Attrib.: Here you can specify if this event is a security one or not and if it is an evacuation event
or not. See

Common Option

to learn more about the security option.

Next Event: Here you can select the event to start after the current one is finished.

Start Impulse: Ticking this option allows user to close an output contact (Logic Output channel)
in two different manner. Static will close it until the event stop and Pulse will generate a closing
pulse whose length can be defined from 50 to 60000 ms.

Stop Impulse: This option is used to create a closing contact pulse when the event is finished.
The length of the pulse can be defined from 50 to 60000 ms.

ACK Relay: You can specify here an logic output channel that will be closed when the event is
active.

Busy Relay: Here you can specify an Logic Output Channel relay that will be closed as soon as
a higher priority event is active in one of the pre-define zones. To learn more about output relay,
please read the

How To Use Output Relay.

Conflict: You can choose between Cancel All or Coexist.

Pre Chime: Before a call you can add a chime message. Here, if Pre Chime Enable is selected,
you can select which message will be used as pre chime.

Post Chime: After a call you can add a chime message. Here, if Post Chime Enable is selected,
you can select which message will be used as post chime

Pre-define Zone: If ticked, you can choose pre defined zone with the zone selector.

Zone Selection: Here you can specify the zone(s) where the call will be played

Music ON

The Music On event allows to start music source 1 or 2 with any type of trigger. Music sources will start
playing in pre-defined zone(s) chosen in the Music Event window.