For example L25 means clear zones grouped on code 5 if they are occupied by channel 2,
L41,3 means clear zones grouped on codes 1 and 3 occupied by channel 4. The answer is the
same as previous clear command.

Normal level for all the channels: command string = N000

The normal level value is setup inside the slave configuration, answer is always ACK CR.

Loud level for all the channels: commandstring=S000

The loud level value is setup inside the slave configuration, answer is always ACK CR.

5.9.2

Use RS232 Ports

5.9.2.1

Notifier

How to set the RS232 port of DIVA to communicate with a Notifier fire panel.

To access the RS232 port settings, click on the RS-232 Port1 or RS-232 Port2 tabs. As the
settings are the same for both ports, only one will be introduced.

Procedure:

On RS-232 Port 1, choose the Notifier protocol wit the protocol drop-down menu.

Select the same Baud Rate choosen on the fire panel. In the Notifier protocol, the baud rate can
be chosen according to the needs.

Data bit should be set to 8.

Stop bit should be set to 1.