Modbus – ATEIS DIVA8G2 User Manual

Page 274

Advertising
background image

DIVA system

274

© 2012 ATEÏS

Parity should be set to "No Parity".

More information about the Notifier protocol and how to use it with DIVA can be found in the

communication protocols chapter.

The serial port pinning information can be found in

each connectors on back panel.

5.9.2.2

Modbus

How to set the RS232 port of DIVA to communicate with a Modbus server.

To access the RS232 port settings, click on the RS-232 Port1 or RS-232 Port2 tabs. As the
settings are the same for both ports, only one will be introduced.

Procedure:

On RS-232 Port 1, choose the Modbus protocol with the protocol drop-down menu.

Select the appropriate Baud Rate: for Modbus choose 9600.

Data bit should be set to 8.

Stop bit should be set to 1.

Parity should be set to "No Parity".

More information about the Modbus protocol and how to use it with DIVA can be found in the

communication protocols chapter.

The serial port pinning information can be found in

each connectors on back panel.