Honeywell DCP552 Mark II User Manual

Page 107

Advertising
background image

7-8

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

PA 93

Auto-tuning (CH2)

93

0: AT not performed

1: standard AT performed on currently used PID group in

mode other than READY mode.

2: AT writing overshoot-proof PID values to currently used

PID groups in mode other than READY mode performed.

3: Standard AT performed on PID groups A1 to A7 in READY mode.

4: AT writing overshoot-proof PID values to PID groups

A1 to A7 in READY mode continuously performed.

[Description:]

Т-----У is displayed for models with CP compensation and setting cannot be performed.

0

PA 94

Auto-tuning MV lower limit

(CH2)

94

-5.0 to upper limit %

[Description:]

Т-----У is displayed for models with CP compensation and setting cannot be performed.

Valid when setup data

C22

setting is set to 1, 3 or 5.

0.0

PA 95

Auto-tuning MV upper limit

(CH2)

95

Lower limit to +105%

[Description:]

Т-----У is displayed for models with CP compensation and setting cannot be performed.

Valid when setup data

C22

setting is set to 1, 3 or 5.

100.0

PA 96

PID computation initialize

(CH2)

96

0: No initialization during advance processing and PID group change

1: Initializes during advance processing but not during PID group change

2: No initialization during advance processing but

initializes during PID group change

3: Initializes both during advance processing and PID group change

0

PA 97

CP computation

compensation

97

0: No compensation

1: compensates

[Description:]

Т-----У is displayed for models without CP compensation and setting cannot be performed.

0

PA 98

CP value (PV) display lower

limit value

98

0 to upper limit SPU (CH2)

[Description:]

Т-----У is displayed for models without CP compensation and setting cannot be performed.

0.000

PA 99

CP value (PV) display upper

limit value

99

lower limit to 4000 SPU (CH2)

[Description:]

Т-----У is displayed for models without CP compensation and setting cannot be performed.

4.000

PA 100

Gas constant

100

10.0 to 50.0 %

[Description:]

Т-----У is displayed for models without CP compensation and setting cannot be performed.

23.5

PA 101

CP computation compensation No. 1 compensation point

101

No. 1 compensation point

: 0 SPU (CH2) (tied)

No. 2 to 9compensation point : 0 to +2000 SPU (CH2)

NO. 10 compensation point

: 2000 SPU (CH2) (tied)

NO. 1 to 10 compensation amount

: -1000 to +1000 SPU (CH2)

[Description:]

бТ-----У is displayed for models without CP compensation

and setting cannot be performed.

бТ-----У is displayed when

PA97

is set to 0 and setting

cannot be performed.

0.000

PA 102

CP computation compensation No. 1 compensation amount

102

0.000

PA 103

CP computation compensation No. 2 compensation point

103

0.200

PA 104

CP computation compensation No. 2 compensation amount

104

0.000

PA 105

CP computation compensation No. 3 compensation point

105

0.400

PA 106

CP computation compensation No. 3 compensation amount

106

0.000

PA 107

CP computation compensation No. 4 compensation point

107

0.600

PA 108

CP computation compensation No. 4 compensation amount

108

0.000

PA 109

CP computation compensation No. 5 compensation point

109

PA 110

CP computation compensation No. 5 compensation amount

110

PA 111

CP computation compensation No. 6 compensation point

111

PA 112

CP computation compensation No. 6 compensation amount

112

PA 113

CP computation compensation No. 7 compensation point

113

PA 114

CP computation compensation No. 7 compensation amount

114

PA 115

CP computation compensation No. 8 compensation point

115

PA 116

CP computation compensation No. 8 compensation amount

116

PA 117

CP computation compensation No. 9compensation point

117

PA 118

CP computation compensation No. 9compensation amount

118

PA 119

CP computation compensation No. 10 compensation point

119

PA 120

CP computation compensation No. 10 compensation amount

120

0.800
0.000
1.000
0.000
1.200
0.000
1.400
0.000
1.600
0.000
2.000
0.000

Chapter 7. PARAMETER SETUP