7 control output connection, 4 - 7 control output connection, Warning – Honeywell DCP552 Mark II User Manual

Page 37

Advertising
background image

4 - 7

Control Output Connection

Current output (5G, 5S)

Voltage output (6D)

Handling Precautions

The voltage output is a constant current circuit inside. The SSR used is set
to an optimum voltage to meet the requirements of the load. Enter the
value in the setup data. A normal SSR voltage has been set at the factory
before shipment.

Open collector output (8D)

Handling Precautions

• Do not short-circuit the positive (+) terminal of the external power supply

to terminal (43) on the

DCP552

. Doing so causes the open collector

outputs to malfunction. (There is no short-circuit preventing circuit
inside.)

• When connecting a semiconductor load such as a programmable

controller (sequencer), select a module in which the current directions
match.
Use one made inoperative by the leakage current produced when the
digital outputs are shut off.

4-9

43

+ -

Load

44

4 to 20mA DC

Load resistance

less than 6009

4 to 20mA DC

Load resistance

less than 6009

45

+ -

Load

46

+

-

+

-

CH2

CH1

Chapter 4. WIRING

WARNING

Be sure to turn off the power supply when you are installing or removing the
controller.
Failure to do so may cause electric shock or fire.

43

+

44

2 to 22mA DC

With current value

adjustment function

(Setup data

C91

)

SSR

+

-

-

45

+

46

2 to 22mA DC

With current value

adjustment function

(Setup data

C92

)

SSR

+ -

-

CH1

CH2

43

12 to 24V DC

+ -

44

Max. load current : 100mA

Leakage current

when off : less than 0.1mA

Load

45

12 to 24V DC

+ -

46

Max. load current : 100mA

Leakage current

when off : less than 0.1mA

Load

CH2

CH1

Advertising