11-1

Chapter 11. SPECIFICATIONS

11 - 1

Specifications

Item

Specifications

Program

section

Input section

No. of programs

49 programs x 2 channels

No. of segments

99 segments/1 program, or total of 2000 segments

Segment setting system

RAMP-X: Setting by set points (SP) and time.

RAMP-T: Setting by set points (SP) and slope (

θ

).

RAMP-E: Setting by set points (SP) or ÆSP per pulse of external switch input.

Segment time

0 to 500 hours 00 min, 0 to 500 min 00sec, or 0.0 to 3000.0sec (Time unit is switchable.)

Segment slope

1 to 10000U/hours, 1 to 10000U/min, or 1 to 10000U/sec (Time unit is switchable.)

Segment ÆSP

1 to 10000U/1 pulse

No. of sub-function

4000 settings

Event (16 point)

Operating point set as specified by event type.

PID group setting

Group 0 (continuing from previous segment), groups 1 to 9, group A (automatic

changeover) and ON-OFF control settable.

Output limiter group

Group 0 (continuing from previous segment), groups 1 to 9 settable

G.SOAK

Type (start point, end point, all) and G.SOAK width 0 to 1000U settable

PV shift

Ð10000 to +10000U settable

Repeat

Return segment number and repeat count settable.

PV start

Type settable for each program (ascending, descending and bi-directional)

Cycle

Cycle count number settable for each program

Pattern link

Program numbers 0 to 49 (program 0 without link) settable for each program

Tag

8 characters consisting of alphanumerics, and symbols settable for each program

Basic time accuracy

±0.01% (segment time setting = 0, repeat; each cycle and repeat slows the process by 0.1sec)

Input type

Multi-range of thermocouple, resistance temperature detector, DC voltage, and

DC current (see page 2-8.)

Input sampling cycle

0.1s

Input bias current

Thermocouple, DC voltage input: Max. ± 1.3

µ

A (peak value, under standard

conditions). The range higher than 1V is Max. Ð3

µ

A.

Input impedance

Dc current input: about 50½ (under the action conditions)

Measurement current

RTD input: approx. 1mA, Current input on terminal A. (under operating conditions)

Influence of wiring

resistance

Thermocouple, DC voltage input:

Resistance temperature detector input:

Resistance temperature

detector input

Allowable wiring resistance

¥ The ranges except F01, F33, P01, and P33 are lower than 85½.

(Includes the zener barrier resistor value. However, spot adjustment is

needed.)

¥ The ranges of F01, F33, P01, and P33 are lower than 10½.

Allowable parallel resistance

Thermocouple disconnection detection allowable parallel resistance : Higher than 1M

Max. allowable input

Thermocouple, DC voltage input:Ð5 to +15V DC

DC current input

: 50mA DC, 2.5V DC

Burn out

Burnout on/off selectable

Range over assessment

100% FS or more: upscaled

Ð10% FS or less : downscaled

(However, inputs in the F50 range are not downscaled.)

Cold junction compensation accuracy

± 0.5¡C (under standard conditions)

Sub-function function

Event, PID group, output limiter group, G.SOAK, PV shift, repeat

Thermocouple

DC voltage (lower than 1V range)

DC voltage (5V range)

DC voltage (10V range)

: 0.5

µ

V/½

: 0.5

µ

V/½

: 3

µ

V/½

: 6

µ

V/½

Max. ± 0.01% FS/½ within wire resistor 0 to 10½

The ranges of F01, F33, P01, and P33 are Max. ± 0.02% FS/½

.