Dcp552 parameter work sheet, Fixed command control data (ch1) setting, Fixed command control data (ch2) setting – Honeywell DCP552 Mark II User Manual

Page 228

Advertising
background image

19

DCP552 Parameter Work Sheet

No. Item code

Item

Factory default User

Settings and descriptions

settings

settings

1

ConSt

Control mode

0

0 : Program run mode
1 : Fixed command control mode

2

SP

Set point

0

Within setup

C66

to

C67

setting (SP limit)

3

P

Proportional band

100.0

0.0 to 1000.0%
(0.0 : On-off control)

4

I

Integral time

0

0 to 3600sec
(0: no integral operation)

5

d

Derivative time

0

0 to 1200sec
(0: no derivative operation)

6

rE

Manual reset

50.0

0.0 to 100.0%

7

oL

Manipulated variable lower limit 0.0

–5.0 to upper limit %

8

oH

Manipulated variable upper limit 100.0

Lower limit to +105.0%

Fixed command control data (CH1) setting

No. Item code

Item

Factory default User

Settings and descriptions

settings

settings

1

ConSt

Control mode

0

0 : Program run mode
1 : Fixed command control mode

2

SP

Set point

0

Within setup

C69

to

C70

setting (SP limit)

3

P

Proportional band

100.0

0.0 to 1000.0%
(0.0 : On-off control)

4

I

Integral time

0

0 to 3600sec
(0: no integral operation)

5

d

Derivative time

0

0 to 1200sec
(0: no derivative operation)

6

rE

Manual reset

50.0

0.0 to 100.0%

7

oL

Manipulated variable lower limit 0.0

–5.0 to upper limit %

8

oH

Manipulated variable upper limit 100.0

Lower limit to +105.0%

Fixed command control data (CH2) setting