Sensor check (model with cp compensation) – Honeywell DCP552 Mark II User Manual

Page 77

Advertising
background image

5-31

O

2

sensor check (model with CP compensation)

Objective

As the O

2

sensor starts to deteriorate, its output impedance increases. This function

checks sensor output impedance and turns on the O

2

sensor error event when the

impedance exceeds 130kΩ.

Setting

•One of the values set for setup data

C71

to

C74

is set to 11 to assign the O

2

sensor check to an external switch.

•One of the values set for event configuration data setting

E01-t

to

E16-t

is set to

142 to assign an O

2

sensor error event.

Operation

•Two methods are used to perform an O

2

sensor check. In one method the external

switch which has been assigned the O

2

sensor check function goes from OFF to

ON. This is called a constant check.

•The other method the external switch is turned on each 24-hour period. This is

called an automatic check.

•The impedance is checked when PV1 is 800 °C or more and the O

2

input is

1000mV or higher.

•The O

2

sensor error event goes on when sensor impedance exceeds 130k;Ω

otherwise it remains off.

•The constant check method is shown below.

•The automatic check method is shown below.

Chapter 5. FUNCTIONS

Sensor

replacement

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

ON

ON

OFF

130k½

External switch

O

2

sensor check

O

2

sensor

impedance

Event output

(O

2

sensor error)

Impedance

Time

OFF

ON

OFF

OFF

ON

ON

OFF

24 hours 24 hours

24 hours

Sensor

replacement

130k½

External switch

O

2

sensor check

O

2

sensor

impedance

Event output

(O

2

sensor error)

Impedance

Time