Writing into EEPROM

(1)

Press

SETUP key

until the PROG/SEG display shows (

02-09

).

(2)

Scroll

,

,

,

, keys

to show (

1.1.1.1.

) on upper display.

(3)

Press

ENTER key

.

Current output calibration

Scroll

,

,

,

, keys

to show (

6.0.6.6.

) on the upper display, then press

ENTER key

.

Connect the digital ammeter across terminals (See Figure 12-9).

OUT CH1 output calibration

(1)

Press

SETUP key

until the PROG/SEG display shows (

06-01

).

Scroll

,

,

,

, keys

until meter indicates 4.00mA, then press

ENTER

key

.

(2)

Press

SETUP key

until the PROG/SEG display shows (

06-02

).

Scroll

,

,

,

, keys

until meter indicates 20.00mA, then press

ENTER

key

.

OUT CH2 output calibration

(1)

Press

SETUP key

until the PROG/SEG display shows (

06-03

).

Scroll

,

,

,

, keys

until meter indicates 4.00mA, then press

ENTER

key

.

(2)

Press

SETUP key

until the PROG/SEG display shows (

06-04

).

Scroll

,

,

,

, keys

until meter indicates 20.00mA, then press

ENTER

key

.

AUX CH1 output calibration

(1)

Press

SETUP key

until the PROG/SEG display shows (

06-05)

.

Scroll

,

,

,

, keys

until meter indicates 4.00mA, then press

ENTER

key

.

(2)

Press

SETUP key

until the PROG/SEG display shows (

06-06

).

Scroll

,

,

,

, keys

until meter indicates 20.00mA, then press

ENTER

key

.

AUX CH2 output calibration

(1)

Press

SETUP key

until the PROG/SEG display shows (

06-07)

.

Scroll

,

,

,

, keys

until meter indicates 4.00mA, then press

ENTER

key

.

(2)

Press

SETUP key

until the PROG/SEG display shows (

06-08

).

Scroll

,

,

,

, keys

until meter indicates 20.00mA, then press

ENTER

key

.

Chapter 12. CALIBRATION