7-28

0: Displayed

1: Not displayed

0

C 57

57

Programming item

event

0: Displayed

1: Not displayed

0

C 58

58

Programming item

PID group, output limiter group

0: Displayed

1: Not displayed

0

C 59

59

Programming item

G.SOAK, PV shift, repeat

0: Displayed

1: Not displayed

0

C 60

60

Programming item

PV start, cycle, pattern link

0: RAMP-X and RAMP-T (q) combined

1: RAMP-X and RAMP-E (ÆSP) combined

0

C 61

61

Programming system

0: hours, min (SPU/hour for RAMP-T)

1: min, sec (SPU/min for RAMP-T)

2: 0.1 sec (SPU/sec for RAMP-T)

0

C 62

62

Programming time unit

0: remaining segment time

1: total operation time (after READY ® RUN start)

0

C 63

63

Time display

(display panel 1 and 2)

0 to 16

0 indicates no CH2 event

[Description:]

When a change in set values cause multiple output

points for a code event to overlap the CH1 and CH2

division, the event configuration setting output points is

changed so that only CH1 is used.

0

C 64

64

Event no. division (first CH2

number)

0 to 4

A setting of 0 means no decimal point and a setting

between 1 and 4 indicates the number of decimal digits.

[Description:]

This setting is reflected in PVU (SPU (CH1)) units.

1

C 65

65

SP decimal point position

(CH1)

PV1 range

lower limit

C 66

66

SP limit lower limit (CH1)

-19999 to +20000 SPU (CH1)

[Description:]

When

C01

to

C06

are set,

C66

and

C67

are

automatically set as the upper limit and lower limit of the

range.

PV1 range

upper limit

C 67

67

SP limit upper limit (CH1)

PV2 range

lower limit

C 69

69

SP limit lower limit (CH2)

-19999 to +20000 SPU (CH2) on a model without CP

compensation.

0 to 2000 SPU(CH2) on a model with CP compensation.

[Description:]

When

C11

to

C16

are set,

C69

and

C70

are

automatically set as the upper limit and lower limit of the

PV1 range.

The factory default setting for models with CP

compensation is

C69

=0.000,

C70

=2.000.

0

C 71

71

External switch input RSW5

0 : NOP (does not function)

1 : RAMP-E

2 : FAST

3 : G.SOAK is cleared using OR

4 : G.SOAK is cleared using AND

5 : MANUAL/AUTO

6 : AT start/terminate

7 : NOP (does not function)

8 : Auto load

9 : NOP (does not function)

10: NOP (does not function)

11: O

2

sensor check

PV2 range

upper limit

C 70

70

SP limit upper limit (CH2)

0 to 4 on a model without CP compensation.

0 to 3 on a model with CP compensation.

A setting of 0 means no decimal point and a setting

between 1 and 4 indicates the number of decimal digits.

[Description:]

This setting is reflected in PVU (SPU (CH2)) units.

The factory default setting for models without CP

compensation is 1.

The factory default setting for models without CP

compensation is 3.

1 or 3

C 68

68

SP decimal point position

(CH2)

0

C 72

72

External switch input RSW6

0

C 73

73

External switch input RSW7

0

C 74

74

External switch input RSW8

Item code

Item

No.

User

settings

Settings and descriptions

Factory default

settings

0: BCD4 bits + BCD2 bits

1: binary 7 bits

0

C 75

75

External switch input RSW9

to 14 (program selection)

Chapter 7. PARAMETER SETUP