Chapter 5. FUNCTIONS

G.SOAK (Guarantee soak)

Separate G.SOAK settings can be made in CH1 and CH2 programs.
G.SOAK on/off state, type and G.SOAK width is set by the segment. G.SOAK are
of three types: segment start point, segment end point and the entire segment.
G.SOAK time is set using the variable parameter

PA46

setting. Any offset

between SP and PV triggers a G.SOAK wait which narrows the distance between
SP and PV to guarantee the segment execution time. G.SOAK operates not only
on SOAK but also on RAMP segments.
Note, however, that in FAST mode a G.SOAK setting does not trigger a G.SOAK
wait.
When a G.SOAK wait occurs in one channel in sync mode (variable parameter

PA04

is set to 1), the program in the other channel is halted.

G.SOAK can be cleared with an external switch input. The following types of
clearing conditions can be selected using setup data setting

C71

to

C74

.

(1) G.SOAK is cleared when an external switch contact is set to on or when PV

meets the G.SOAK clearing conditions.

(2) G.SOAK is cleared when an external switch contact is set to on and PV meets

the G.SOAK clearing conditions.

• G.SOAK at start of segment

PV and SP are compared at the beginning of the segment. The segment starts
when the absolute value of the difference continues beyond the G.SOAK time
and becomes narrower than G.SOAK width.
A G.SOAK wait state continues until these conditions are met which is
announced by the flashing of the linear LED on the left of the profile display.
The operating condition is the same as HOLD at the beginning of a segment
(time = 0).

Time

SP

G.SOAK
width

G.SOAK
width

SP

PV

Segment
setting time

Segment
executing time

G.SOAK wait time