10--11

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

10.3.5 SSBM Shutdown to Bypass

1.

On SSBM, turn the

SYSTEM MODE key switch to BYPASS momentarily.

2.

Observe CBS opens, CBP closes.

3.

On SSBM monitor screen, verify On Bypass message appears. System is now

on bypass.

4.

On all but the last UPM, turn the

MODE key switch to BYPASS for three

seconds.

5.

Verify that UPS breakers CB1 and CB3 and battery breaker CB2 (MBB) are

open and the UPM powers down.

6.

To shut down last UPM, press last UPM

LOAD OFF pushbutton.

7.

Verify that UPS breakers CB1 and CB3 and battery breaker CB2 (MBB) are

open and the UPM powers down.

WARNING:

Power is present at UPM CB1 input, until

upstream UPM input feeder circuit

breaker is opened.

10.3.6 Restarting a Single UPM

1.

Close upstream UPM input feeder breaker.

2.

Observe UPM monitor screen becoming active as an indication of logic power.

3.

Verify UPM is shown on the SSBM mimic screen.

4.

On UPM, set

BATTERY switch to ENABLE.

5.

On UPM, turn

MODE key switch to NORMAL for three seconds

6.

Confirm the UPS breaker CB1 has closed by viewing breaker position on LCD

Mimic screen.

The rectifier and input/rectifier cooling blowers turn on.

7.

Confirm UPS Battery Breaker CB2 (MBB) has closed by viewing breaker

position on LCD Mimic screen.
NOTE: If CB2 is a manual battery breaker, manually close CB2 after UPM

Battery Disconnected alarm and notification is received.

The inverter and output/inverter cooling blowers turn on. When the inverter reaches

full voltage, UPS breaker CB3 closes. It takes less than 1 minute for the UPS to

achieve Normal mode. If UPS is not in Autorestart, turn the

MODE key switch to

NORMAL for three seconds to transfer to Normal mode.

8.

The UPM is now operating in Normal mode.

9.

On SSBM mimic screen, check for presence of UPM.