3 smb circuit breakers, 4 fully rated static switch, 5 emergency upm off – Powerware 9315s User Manual

Page 72: 6 customer interface panel, 7 customer convenience outlet, 8 installation features

Advertising
background image

8--6

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

8.2.3

SMB Circuit Breakers

The System Maintenance Bypass (SMB) contains two breakers: the Maintenance

Bypass Breaker (MBP) and the Maintenance Isolation Breaker (MIS). The MIS

connects the output of the UPMs to the critical load via CBS. The MBP is used as

the bypass in the event the output of the SSBM is not available and to supply the

critical load during SSBM maintenance. These breakers are manually controlled

through electrical interlocks which include a control switch mounted inside the

Control Section on the A1 Panel.

8.2.4

Fully Rated Static Switch

The fully rated static switch is connected in series with the FBP and is only gated

on during emergency transfers from Normal to Bypass mode. The fully rated static

switch is electrically controlled by the SSBM and is automatic in operation.

8.2.5

EMERGENCY UPM OFF

An

EMERGENCY UPM OFF pushbutton is provided for situations where you must

instantaneously control the UPM and SSBM output. The pushbutton is located on

the front of the SSBM for quick access and is covered with a clear plastic shield to

prevent inadvertent operation. The shield must be raised before pressing the

pushbutton. The

EMERGENCY UPM OFF pushbutton is described in detail in

Chapter 10, “Operating Instructions for the Parallel Capacity/Redundant System.”

8.2.6

Customer Interface Panel

PowerNet

Two redundant control networks connect UPM to UPM and UPM to the SSBM. Each

network requires only one shielded twisted pair of wires. Refer to Appendix A, drawing

164201335---4 for further information.

Computer Interface

Two serial communications ports are standard on all units, and are electrically isolated

from the SSBM. You can use these ports to link the SSBM to the features described in

Chapter 13, “Serial Communications” and Chapter 14, “Remote Notification.”

Summary Alarm Contacts

Alarm contacts are provided for connection to equipment at your facility, such as a

light, an audible alarm, or a computer terminal. The equipment you connect to these

contacts alerts you to an SSBM alarm. This feature is described further in Chapter 11,

“Using Features and Options.”

Building Alarm Monitoring

You can connect your facility’s alarm system contacts to six inputs in the SSBM. The

SSBM uses these inputs to monitor your building alarms in addition to the SSBM

status. This feature is described further in Chapter 11, “Using Features and Options.”

8.2.7

Customer Convenience Outlet

An uninterruptible 120VAC, 0.2 amp, fuse-protected convenience outlet is provided

to supply power to the optional modem. It is located adjacent to the Customer

Interface Panel.

8.2.8

Installation Features

Power wiring can be routed through the top or bottom of each cabinet. External

sensing and monitoring control wire must be installed in accordance with Class 1

wiring methods. Class 1 wiring can be routed through the top or bottom of each

cabinet.

Advertising