2 manual start – Powerware 9315s User Manual

Page 92

Advertising
background image

10--2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

10.2.2 Manual Start

1.

Perform the Initial Setup procedures.

2.

On SSBM, turn the

SYSTEM MODE key switch to BYPASS momentarily.

If a bypass source is available when you turn the

SYSTEM MODE key switch to

BYPASS, the critical load is immediately supplied by the bypass source in Bypass

mode until the the UPMs are available and the SSBM has been manually transferred

to Normal mode. The status indicators on the SSBM monitor screen indicate when

the

Parallel Capacity/Redundant system

is in Bypass mode and Normal mode.

3.

Observe that CBP and FBP have closed.

4.

On first UPM, close CB1.

5.

Observe UPM monitor screen becoming active as an indication of logic power.

6.

Verify UPM is shown on the SSBM mimic screen.

7.

On first UPM, set

BATTERY switch to NORMAL.

8.

On first UPM, set

MODE switch to NORMAL.

9.

On first UPM, turn the

START switch to the right for 2 seconds and then

release.

10.

When UPM Battery Disconnected alarm and notification is received, close first

UPM battery disconnect breaker.

11.

On first UPM, turn the

START switch to the right momentarily.

The rectifier turns on, then the inverter turns on. When the inverter reaches full

voltage, K3 closes. Logic power is supplied and the UPM is ready to supply power

to the critical load. It takes less than 1 minute for the UPM to achieve Normal mode.

12.

Start remaining UPMs by repeating steps 4 through 10.

13.

On SSBM monitor screen, check for On Bypass, UPMs Ready message.

14.

If message appears, turn the SSBM

SYSTEM MODE key switch to NORMAL

momentarily.

15.

Observe that breaker CBS closes and breaker CBP opens. System is now in

Normal mode, with the critical load being supplied power from the UPMs.