Responding to System Events

12.1

General

When the Parallel Capacity/Redundant system is running in Normal mode, it

continually monitors itself and the incoming utility power. In Battery or Bypass

modes, the Switchboard System Bypass Module (SSBM) may issue alarms to let

you know exactly what event caused the change from Normal mode. System

events on the SSBM can be indicated by horns, lights, messages, or all three.

Select

Active from the Events menu on the LCD screen to look at the Active

System Events screen. This screen shows any currently active alarms, notices,

or commands.

NOTE: Refer to the applicable Powerware9315 UPS Operation manual provided

with the UPMs, for UPM system events.

12.2

System Event Horns

The system event horn beeps according to the type of event it is signifying:

When the UPS detects an alarm that requires your attention, the horn beeps at

½-second intervals.

When a notice occurs, the horn beeps at 2-second intervals.

12.3

System Event Lights

The status indicators on the SSBM Control Panel work in conjunction with the

event horn to let you know when the Parallel Capacity/Redundant system is

operating in any mode other than Normal. Only the Normal indicator is visible

during normal Parallel Capacity/Redundant system operation. The others light to

indicate alarms or events. When an alarm occurs, you should first check these

indicators to see what type of event has taken place. (For descriptions of the

status indicators, refer to the “Reading the Status Indicators” section of Chapter 9.)