DESCRIPTION:

DRAWING NO:

SHEET:

SSBM CUSTOMER INTERFACE PANEL

6 of 6

164201373---4

A---18

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Table J. Customer Interface Panel Inputs and Outputs (Cont’d)

Terminal

Block

TB Pin #

Name

Description

1

ON UPS

Contacts used to indicate On UPS status of

2

ON UPS RTN

Contacts used to indicate On UPS status of

Parallel Capacity/Redundant System

3

ON BYPASS

Contacts used to indicate On Bypass status of

4

ON BYPASS RTN

Contacts used to indicate On Bypass status of

Parallel Capacity/Redundant System (See Note 6)

TB4

5

RELAY # 1 NC

G

l

NO

d NC l

TB4

6

RELAY # 1 NO

General purpose NO and NC relay

contacts (See Note 4)

7

RELAY # 1 RTN

contacts. (See Note 4)

8

RELAY # 2 NC

G

l

NO

d NC l

9

RELAY # 2 NO

General purpose NO and NC relay

contacts (See Note 5)

10

RELAY # 2 RTN

contacts. (See Note 5)

1

Bypass ∅ A

2

Bypass ∅ B

3

Bypass ∅ C

Sync Reference Voltage for Optional Powerware

4

Sync Reference ∅ A

Sync Reference Voltage for Optional Powerware

9315 Sync Control Connections.

TB6

5

Sync Reference ∅ B

9315 Sync Control Connections.

Al

d f O i

l P

H Ti C

l

6

Sync Reference ∅ C

Also used for Optional Powerware Hot-Tie Control

and Hot Tie with Sync Control connections

7

Output ∅ A

and Hot-Tie with Sync Control connections.

8

Output ∅ B

9

Output ∅ C

1

+12VDC

2

+12VDC RTN

3

+12VDC

4

+12VDC RTN

TB7

5

+12VDC

Optional CAN Power Supply Panel (A13) Terminal

Block for Powerware 9315 (500 kVA 750 kVA)

TB7

6

+12VDC RTN

Block for Powerware 9315 (500 kVA---750 kVA)

Models only

7

+12VDC

Models only

8

+12VDC RTN

9

+12VDC

10

+12VDC RTN

NOTES:

5.

Relay 1 is normally deenergized and is only energized for an alarm condition.

6.

Relay 2 is normally energized and is only deenergized for an alarm condition.

7.

If the SSBM is setup for a Powerware Sync Control, the ON BYPASS contact is used for Sync

Control and is not available for customer use.