Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

7.3

Optional Modes of Parallel Operation:

Maintenance Bypass and Redundant CBP

There are two optional modes of operation in this Parallel Capacity/Redundant

system:

•

In

Maintenance Bypass mode (optional), the SMB bypass supplies the load and

isolates the SSBM and UPMs for maintenance purposes.

•

In

Redundant CBP mode (optional), if the CBP breaker fails to close during a

manual or automatic operation, the SSBM automatically closes the MBP

breaker to maintain power to the critical load.

The following descriptions provide the Parallel Capacity/Redundant system

optional operating mode differences.