5--2

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

5.2

To install a RIM:

1.

Securely mount the RIM.

2.

Install wiring from the RIM using ½-in. conduit through the cable entry panels

in the top of the SSBM control section (refer to the enclosed switchboard

vendor drawings for the location of the conduit landing plate).

3.

If not already installed, locate the RMP adapter cable assembly (see Figure

5---2) in the spare parts kit. Mate the DB---9 connector on the back of the

terminal block to the DB---9 connector (Port 1) on the Customer Interface Panel

of the SSBM (refer to Drawing 164201373---4 in Appendix A). Use two screws

from the spare parts kit to secure the terminal block bracket to the Customer

Interface Panel.

Connect to

Port 1 (DB---9) on

Customer Interface Panel

TERMINAL

BLOCK

FUSE

(TB3)

Figure 5---2. Terminal Block Bracket