6 system configuration, 1 system configuration mode main menu, 2 program building alarms – Powerware 9315s User Manual

Page 132

Advertising
background image

13--10

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

13.6

System Configuration

The System Configuration mode allows you to modify special functions in your

SSBM. These functions include programming of building alarms, customizing

building alarm messages, adjusting the nominal output voltage, and scheduling

battery tests. The menus provided and their function are described in this section.

13.6.1 System Configuration Mode Main Menu

When the System Configuration mode is selected with a terminal attached, you will

be prompted to enter the password for this mode:

Please Enter Password:

The default password is POWER1. You may modify this password using the

change password function in the following menu. When the valid password is

entered, the main menu will be displayed:

Program Mode Main Menu
1. Program Building Alarms
2. Program Unit Name
3. Adjust Output Voltage
4. Change Password
5. Battery Test Setup
6. Modify Low Battery Time
7. Exit Program Mode
Enter Selection:

13.6.2 Program Building Alarms

This menu provides access to all the functions available in the system configuration

mode. If 1 is entered at the prompt, you can program the building alarm functions:

Program Building Alarms

1. Enable/Disable Default Functions
2. Customize Alarm Messages
3. Return to Main Menu
Enter Selection: