6 unit statistics screen, Figure 9 . unit statistics screen – Powerware 9315s User Manual

Page 86

Advertising
background image

9--10

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

9.6.6

Unit Statistics Screen

Select

Unit from the Statistics menu to display a listing of statistics about UPS

operation.
Figure 9---8 shows the Unit Statistics screen.

Uninterruptible Power System

UPS System Normal

Events

Statistics

Graphics Setup

Meters

Statistics

Unit

Start Date:

04 MAY 1997

Number of Incidents:

On Battery < 1 Min.
On Battery 1-4 Min.
On Battery > 4 Min.
Full Batt. Discharge
Building Alarm 1
Building Alarm 2
Building Alarm 3
Building Alarm 4
Building Alarm 5
Building Alarm 6

UPS
Bypass
Battery
Generator
Logic

Availability
UPS
Bypass

0
1
0
0
2
2
3
2
3
3

0
0
0
0

11

9
8
5
8
9

0.99
0.81

48.5

Minutes

Battery

Month Total

DAYS HR MN

Time On:

0035 20 59
0000 00 30
0000 00 02
0000 00 00
0035 21 30

ALARM:

NONE

NOTICES: NONE

15 JUL 1998

09:25:42

Figure 9---8. Unit Statistics Screen

The left column shows the number of UPS incidents for the current month and

since the start date shown at the top of the screen. The top right column shows

the time that the UPS was on bypass, battery, or generator, and the amount of time

the UPS logic has been functioning since the start date. The lower right column

shows the percent of availability of the UPS and the bypass source.