Chapter 11 using features and options, Using features and options, 1 general – Powerware 9315s User Manual

Page 109: 2 building alarm monitoring, 3 general purpose relay contacts

Advertising
background image

11--1

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Using Features and Options

11.1

General

The many standard features of your Parallel Capacity/Redundant system Parallel

Capacity/Redundant system provide consistent, economical, and dependable

power protection. In addition, you can add available options to enhance the

performance of your system. This chapter provides descriptions of some of the

features and options introduced earlier in this manual. Refer to drawings

164201373---4 and 164201373---13 in Appendix A for location of the customer

interface panel and for terminal wiring information.
NOTE: Refer to the applicable Powerware9315 Operation manual provided with

the UPS for UPS features and options

11.2

Building Alarm Monitoring

This standard feature lets you connect the Switchboard System Bypass Module

(SSBM) to your building alarms, such as smoke detectors or overtemperature

alarms. The terminals for external connections are located inside the SSBM on the

customer interface panel.
Regardless of how you assign the building alarms, they display as Building Alarm 1,

Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You

should use twisted pair wires for each alarm input and common.
If the SSBM is equipped for a Powerware Sync Control, Hot-Tie Control, or

continuous duty static switch, not all Building Alarms will be available for customer

use. See Appendix A, Drawing 164201373---4 for affected areas.
If the SSBM is equipped with an optional System Maintenance Bypass (SMB), not

all Building Alarms will be available for customer use. See Appendix A, Drawing

164201373---4 for affected areas.

11.3

General Purpose Relay Contacts

Two general purpose relay contacts are provided as a standard feature on the

SSBM. The alarm contacts (one notice and one alarm) are located inside the

SSBM on the customer interface panel. Refer to drawings 164201373---4 and

164201373---13 in Appendix A for location of the customer interface panel and

for terminal wiring information.
You can specify that each contact be either normally closed (NC) or normally open

(NO). If the state of the contact changes from the state you specify as normal, an signal

is issued. You can connect these contacts to equipment at your facility (such as a light

or an alarm bell) to let you know when an alarm is active on the SSBM. This feature

is useful if the SSBM is located in a remote area where the SSBM alarm horn may not

be heard immediately.
NOTE: In choosing contacts, note that Relay 1 is normally deenergized and is

only energized for an alarm condition. Relay 2 is normally energized and is

only deenergized for an alarm condition.

CAUTION:

Contacts should not be operated in excess of

30 VAC or 42.4V peak AC or DC @ 1A maximum.

11