1 initial setup – Powerware 9315s User Manual

Page 98

Advertising
background image

10--8

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

10.3

Operation of SSBM with

Powerware 9315---625 thru 9315---750 UPMs

10.3.1 Initial Setup

1.

Ensure the Switchboard System Bypass Module (SSBM) circuit breakers are

manually charged and set as follows:

System Output Breaker (CBS)

OPEN

System Bypass Breaker (CBP)

OPEN

Backfeed Protection Breaker (FBP)

OPEN

Maintenance Isolation Breaker (MIS)

CLOSED (optional)

Maintenance Bypass Breaker (MBP)

OPEN (optional)

2.

Ensure the UPS circuit breakers for all UPMs are set as follows:

UPS Input Breaker (CB1)

Open

UPS Battery Breaker (CB2) (MBB)

Open

UPS Output Breaker (CB3)

Open

3.

Ensure the Emergency UPM OFF PUSH TO RESET pushbuttons on the SSBM

and all UPMs are pressed in.

NOTE: When power is applied in the following step, circuit breakers CBS, CBP, and

FBP will charge, if not already charged.

4.

Close upstream UPM and SSBM input feeder circuit breakers.

5.

Observe SSBM monitor screen becoming active and Alarm and Notice

messages scrolling.

6.

Observe all UPM monitor screens become active as an indication of logic

power.

7.

Verify all UPMs are shown on the SSBM mimic screen.