4 system history screen, Figure 9 . event history log screen – Powerware 9315s User Manual

Page 84

Advertising
background image

9--8

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

9.6.4

System History Screen

Select

History from the Events menu to display the Event History Log. The Event

History Log lists up to 400 system events in chronological order, with the most

recent event listed last. The end of the log (the most recent events) appears when

you display the screen, and you must scroll upward to view older event listings.
Figure 9---6 shows the Event History Log screen.

Statistics Graphics Setup

Events

History

Active

Uninterruptible Power System

System Normal

Events

Meters

Event History Log

Event Description

03

03

03
03

03

03

03

16:41:19.3

16:41:20.1

16:41:22.4
16:41:25.5

16:41:26.8

16:41:27.8

16:41:30.4
16:41:29.1

COMMAND: Keyswitch On

STATUS:

Auto Mode

COMMAND: Rectifier Commanded On
STATUS:

Inverter On

STATUS:

Rectifier On

STATUS: Inverter Contactor (3) Closed

STATUS:

Bypass Contactor (K4)

Open

03

STATUS:

Inverter Normal

Battery

48.5

Minutes

Date / Time

May

ALARM:

NONE

NOTICES: NONE

15 JUL 1998

09:25:42

Figure 9---6. Event History Log Screen

A small return arrow (

) appears in the upper right corner of the information area

of the Event History Log screen. This arrow is a reminder that you can press the

pushbutton on the Monitor Panel to toggle the scroll bar between the menu

box and the information area. When the scroll bar is in the information area, the

return arrow is in the menu box. When the scroll bar is in the menu box, the return

arrow is in the information area.
When the scroll bar is in the information area, you can press the and pushbuttons

to scroll through the Event History log.