15.3

Performing Preventive Maintenance

The Parallel Capacity/Redundant system requires very little preventive

maintenance. However, the system should be inspected periodically to verify that

the units are operating normally and that the batteries are in good condition.

Perform the following checks DAILY:

Check the area surrounding the Parallel Capacity/Redundant system. Ensure

the area is not cluttered, allowing free access to the unit.

Ensure the air intakes (vents on the front doors) and exhaust opening

(on top of the UPS cabinet and SSBM) are not blocked.

Ensure there is at least six inches of clearance behind the unit for proper air

circulation.

Ensure the operating environment is within the parameters specified in

Chapter 16, “Product Specifications.”

Ensure the SSBM and UPS modules are in Normal mode (Normal status

indicator is lit). If alarm lamps are lit or the Normal status indicators are not lit,

contact Powerware Customer Support.

Perform the following checks MONTHLY:

Ensure all status indicator lamps are operative. (Press the

and

pushbuttons simultaneously to test the lamps.)

Monitor system parameters as described in Chapter 9, “Using the Control

Panel.”

Check the air filters in UPS modules (located behind the front doors) and

replace them as necessary. The filter size is 16 in. x 20 in. x 1 in.

Record the results of your checks and any corrective actions in a suitable log.

ANNUAL maintenance:
Annual preventive maintenance should be performed only by authorized service

personnel familiar with maintenance and servicing of the Parallel

Capacity/Redundant system. Contact your nearest Powerware field service office

for more information about service offerings.

BATTERY maintenance:
Contact your nearest Powerware field service office for battery maintenance.

Battery replacement and maintenance should be performed only by authorized

service personnel.