Powerware 9315s User Manual

Page 25

Advertising
background image

1--3

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

NOTE: Two tables in Appendix A cover the cables running from the UPM output

terminals to the SSBM module input terminals E8 (

A), E9 (

B), E10 (

C),

and E4 (Neutral)
Table O covers the recommended wiring and conduit sizing based on the

applicable Powerware 9315 Installation manual provided with the UPM. Using

the noted power wiring, Table O shows the number of UPMs that can be

connected to each SSBM model. This number of UPMs is limited by the number

of cables connections for the SSBM module input terminals E8, E9, E10, and

E4 shown in Table C in Appendix A.
If the parallel capacity/redundant system requires the connection of more

UPMs to the SSBM than is shown in Table O, refer to Table P. Table P covers

the recommended wiring and conduit sizing to support connection of the

maximum number of UPMs (up to eight) for each SSBM model.

CAUTION:

The UPM output wiring configurations in Table O in Appendix A do not match

that shown in the applicable Powerware 9315 UPS Installation manual. Review

the planned UPM output power cables to ensure the planned cabling is

compatible with the available number of cable connections at both the UPM

and SSBM terminals.

Powerware UPMs are rated for operation in a 40_C room ambient. For this

reason, Table O and P are based on the entire 3

/ 3W system being housed

in a 40_C room ambient, the use of 90_C copper wire and a 0.80 derating factor

because there are more than three current carrying conductors in a raceway

(NEC Table 310---16 and Notes).
Refer to the applicable Powerware 9315 Installation manual provided with the

UPM for all other UPM power cable requirements (AC input, DC input, and

grounding)

NOTE: Review Table C in Appendix A to ensure the planned power cable

configuration is compatible with the available number of cable connections

at each SSBM and SBM terminal.

NOTE: If additional cable connections are required, consider using FCI HYSTACK

Type ASA ---U adapters. HYSTACK P/N ASA250U covers NEMA 2-hole

terminals for wire sizes from #8 AWG to 250kcmil. HYSTACK P/N ASA800U

covers NEMA 2-hole terminals for wire sizes from #8 AWG to 800kcmil.

Care must be taken in HYSTACK adapters to ensure the required

phase-to-phase clearance of 1 inch and phase-to-ground clearance of

1 inch (1.5 inches in Canada) is maintained.

For external wiring, including the recommended minimum AWG size of external

wiring, see Tables A, B, O, and P in Appendix A. The power wiring connections for

this equipment are rated at 90˚C. If wire is run in an ambient temperature greater

than noted above, higher temperature and/or larger size wire may be necessary.

Control wiring for PowerNet, EPO and optional accessories (such as building

alarms, monitoring interface and Maintenance Bypass control) should be

connected at the customer interface panel at the top of the SSBM Powernode

Panel (A1), which is shown in drawing 164201373---12 in Appendix A.

Advertising