Installing the parallel capacity/redundant system, 1 preliminary installation information – Powerware 9315s User Manual

Page 29

Advertising
background image

2--1

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

Installing the Parallel

Capacity/Redundant System

2.1

Preliminary Installation Information

WARNING:

Installation should be performed only by qualified personnel.

Refer to the following while installing the Parallel Capacity/Redundant system:

Appendix A of this manual for installation drawings and additional installation

notes.

Dimensions in this manual are in millimeters and inches.

Do not tilt the Switchboard System Bypass Module (SSBM), UPMs or other

cabinets more than

¦

10˚during installation.

The conduit landing plates are to be removed to add conduit landing holes as

required. Plate material is generally 16 gauge steel (0.06 in. thick).

The Remote Emergency Power Off (EPO) and the EMERGENCY UPM OFF
pushbuttons open all breakers in the SSBM, shut down the UPMs, and isolates

power from your critical load. Local electrical codes may also require tripping

protective devices upstream from the UPMs.

The SSBM cabinet must be installed on a level, sealed concrete pad or floor.

The floor or pad must be strong enough to prevent sagging or cracking from

the SSBM weight. If the floor area is subject to vibrations, special mounting

must be provided to prevent transmitting the vibrations to the SSBM.

If perforated floor tiles are required for ventilation, place them in front of the

UPMs.

Details about control wiring are provided in each procedure for connecting

options and features. Drawings 164201373---4 through 164201373---7 in

Appendix A identify the control wiring terminations.