6 supervisory contact module – Powerware 9315s User Manual

Page 113

Advertising
background image

11--5

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

11.6

Supervisory Contact Module

An optional Supervisory Contact Module (SCM) establishes an interface between

the Parallel Capacity/Redundant system manufacturer’s equipment and the

customer’s monitor. This interface allows the customer to monitor operational

status of the Parallel Capacity/Redundant system equipment. A maximum of two

monitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 11---1

for the number of accessories permitted. Figure 11---3 shows the SCM, input

connections on TB1, and output connections on TB2.

TB2

Figure 11---3. Supervisory Contact Module

The SCM provides signals for the following indications:

SYSTEM NORMAL

TB2---1 through TB2---3

NO REDUNDANCY

TB2---4 through TB2---6

ON GENERATOR

TB2---7 through TB2---9

BYPASS NOT AVAILABLE TB2---10 through TB2---12

ON BATTERY

TB2---13 through TB2---15

UPS ALARM

TB2---16 through TB2---18

ON BYPASS

TB2---19 through TB2---21

SHUTDOWN IMMINENT

TB2---22 through TB2---24

Refer to the applicable Powerware 9315 Installation manual chapter,

Installing a

Supervisory Contact Module, for TB2 contact configurations.