DESCRIPTION:

DRAWING NO:

SHEET:

SSBM CUSTOMER INTERFACE PANEL

1 of 6

Customer Interface Panel

164201373---4

SSBM

Top View

A---13

Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM

164201373 Rev. A

092402

1.

Two redundant PowerNet control networks connect UPM module to UPM module and

UPM module to the SSBM. Each network requires only one shielded twisted pair of wires.

2.

Refer to drawing 164201373---13 for location of the Customer Interface panel (A1).

3.

Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control

wiring in separate conduits from the power wiring. Install the twisted pair of each

redundant PowerNet network in separate conduits. The wire should be rated at 24 volts,

1 amp minimum. The recommended wire for the PowerNet network is shielded 20 gauge

twisted pair Belden 8762 (Powerware Part Number 175090703) or equivalent. The

recommended wire for the optional Network Power Supply panel (A13) for Powerware

9315---625/750 UPMs is 14 gauge twisted pair.

4.

Control wiring run may not exceed 100 meters.

5.

Refer to sheet 2 for typical control wiring routing. Use Arrangement C for a more robust

network.

6.

Connect control wiring and terminating resistor (if applicable ) to the removable portion of

the terminal block.

7.

Terminate each redundant PowerNet network at the end modules in the system. Use a

120 ohm, 1/4 watt, 5% resistor (Powerware Part Number 141202041). Refer to sheet 2 for

typical termination points.

8.

If SSBM is to be terminated, install terminating resistors onto terminal block TB1. Refer to

sheet 3 for terminal location. Connect each resistor across terminals 1 and 2 and 6 and 7.

9.

Refer to Tables I, J, and K, and to applicable chapters for information about installing

control wiring.

SSBM

Front

of

Port 2

DB---25 Connector

Port 1

DB---9 Connector